9.3.1 Additional heating circuit settings
The settings can be found in the service menu under Device settings►Heating circuit 1-3. Specify settings separately for each heating circuit.
Set the upper and lower limit alarms for the supply temperature sensor and room temperature sensor.
The heating is off in the Summer mode and on in the Winter mode.
Auto/Temp: the mode switches automatically according to the outdoor temperature.
Date: the mode switches automatically according to fixed dates.
Summer: heating is permanently off.
Winter: heating is permanently on.
Su/Wi Time const. specifies a filtered temperature time interval to the heating circuit for measuring the change of the heating circuit.
If you set Date as the summer/winter mode setting, specify the heating start and end dates to the Start date and End date fields.
Reset outside temp. resets the filtered outdoor temperature.
In the Room temp. comp. field, you can set a compensation ratio for the room temperature sensor. The higher the value, the more the deviation between the measured room temperature and the room setpoint will affect the supply water temperature.
Room influence indicates the effect of compensation on the supply water temperature.