9.6 Brine circuit settings
The settings can be found in the service menu, under Device settings ► Source circuit.
You can set the minimum and maximum speed values for the brine circuit circulator pump, within which the speed will remain during charging.
Values from 20 to 70 % are allowed for the minimum speed (factory setting = 40 %), and values from 70 to 100 % are allowed for the maximum speed (factory setting = 100 %).
Free cool pos src specifies the circulator pump speed in free cooling. Values form 20 to 100 % are allowed (factory setting = 100 %).
Free cooling is activated using external contact information (see Connecting the source pump external control).