6 Installing the pipes

Pipe installations must be carried out in accordance with the regulations in force. All connections to the heat pump must be made by using approved threaded couplings only.

Taurus heat pumps are not equipped with shut-off valves. These valves must be installed immediately outside the device to facilitate maintenance.

Install a strainer (dirt separator) in the return water pipes of the charge circuit and the collector to prevent any impurities in the network from entering the heat exchanger and causing a blockage in the exchanger. To facilitate the cleaning of the strainer, install a shut-off valve near the strainer.

If the system contains more than one heat pump, or a Gemini heat pump, non-return valves must be installed in the superheating circuit, charge circuit and the collector for each compressor unit. Non-return valves prevent incorrect fluids circulation in the system. For information on how to install non-return valves, please see the connection instructions.

The symbols used in the diagrams are explained in the table below.

Symbol Description Symbol Description Symbol Description

Shut-off valve

Balancing valve

Dirt separator

Vent valve

Change-over valve

Circulator pump

Non-return valve

Control valve

Compressor

Expansion valve

Diaphragm expansion tank

Temperature sensor

Safety valve

Heat exchanger

Pressure gauge

Figure 1. The principle of the Taurus Inverter Pro heat pump system
BO1Collector outlet/outWI2Charge circuit return/in
BI2Collector return/in
WO1Charge circuit supply/out
Figure 2. The principle of the Taurus EVI heat pump system
BO1Collector outlet/outWI2Charge circuit return/in
BI2Collector return/inSO1Superheating circuit supply/out
WO1Charge circuit supply/outSI2Superheating circuit return/in