Output details (without circulator pump) |
0/35 |
Heating output |
kW |
94.9 |
71.4 |
93.6 |
Cooling capacity |
kW |
71.8 |
56.4 |
74.1 |
Supplied power |
kW |
24.3 |
15.8 |
20.5 |
COP |
|
3.9 |
4.5 |
4.6 |
0/55 |
Heating output |
kW |
82.2 |
74.1 |
97.8 |
Cooling capacity |
kW |
55.4 |
50.0 |
65.1 |
Supplied power |
kW |
28.2 |
25.2 |
32.2 |
COP |
|
2.9 |
2.9 |
3.0 |
Output details (in accordance with EN14511) |
0/35 |
Heating output |
kW |
95.0 |
71.5 |
93.6 |
Supplied power |
kW |
24.7 |
16.1 |
20.9 |
COP* |
|
3.8 |
4.4 |
4.5 |
0/45 |
Heating output |
kW |
89.0 |
72.8 |
94.8 |
Supplied power |
kW |
27.4 |
20.1 |
26.0 |
COP* |
|
3.2 |
3.6 |
3.7 |
10/35 |
Heating output |
kW |
99.7 |
85.6 |
108.5 |
Supplied power |
kW |
29.8 |
15.9 |
21.0 |
COP* |
|
4.3 |
5.3 |
5.2 |
10/45 |
Heating output |
kW |
89.1 |
83.6 |
109.1 |
Supplied power |
kW |
32.7 |
20.3 |
26.0 |
COP* |
|
3.6 |
4.2 |
4.2 |
Electrical information |
Rated voltage / electrical connection |
|
400 VAC 3N 50 Hz |
400 VAC 3N 50 Hz |
400 VAC 3N 50 Hz |
Maximum supply current (including the control systems and pumps) – ground source heat use |
Arms |
78 |
70 |
80 |
Maximum supply current (including the control systems and pumps) – other use |
86 |
Recommended fuse size – ground source heat use |
A |
3 x 80 |
3 x 80 |
3 x 80 |
Recommended fuse size– other use |
3 x 100 |
Charge pump power |
W |
608 |
608 |
608 |
Source pump power |
W |
1301 |
1301 |
1301 |
Refrigerant circuit |
Contains fluorinated greenhouse gases |
|
yes |
yes |
yes |
Hermetically sealed |
|
yes |
yes |
yes |
Refrigerant |
|
R513A |
R410A |
R410A |
Global Warming Potential (GWP) of the refrigerant |
|
631 |
2088 |
2088 |
Quantity of refrigerant |
kg |
23 |
9.0 |
9.8 |
CO₂ equivalence |
tonnes CO2e |
14.51 |
18.792 |
20.462 |
Disconnection, overpressure |
MPa |
2.9 |
4.4 |
4.4 |
Difference, overpressure |
MPa |
|
|
|
Disconnection, underpressure |
MPa |
0.05 |
0.23 |
0.23 |
Difference, underpressure |
MPa |
|
|
|
Compressor |
Number of compressors |
|
1 |
2 |
2 |
Compressor type |
|
Piston |
Scroll |
Scroll |
Compressor oil |
|
POE |
POE |
POE |
Amount of oil |
L |
4.3 |
6.8 |
6.8 |
Collector |
Maximum pressure |
MPa |
0.6 (6 bar) |
0.6 (6 bar) |
0.6 (6 bar) |
Rated flow |
l/s |
4.3 |
3.4 |
4.4 |
Maximum external pressure loss at rated flow |
kPa |
120 |
130 |
120 |
Minimum input temperature of brine |
°C |
–5 |
–5 |
–5 |
Maximum input temperature of brine |
°C |
+30 |
+20 |
+20 |
Charge circuit |
Maximum pressure |
MPa |
0.6 (6 bar) |
0.6 (6 bar) |
0.6 (6 bar) |
Rated flow |
|
3.2 |
2.4 |
3.2 |
Maximum external pressure loss at rated flow |
|
65 |
85 |
55 |