11.1 Troubleshooting

If there are no special alerts on the display, perform the following basic actions:

  1. Check all switches.
  2. Check the fuses of the building and the heat pump.
  3. Check the residual current device.
Problem Possible cause Corrective action
Low room temperature The heat pump is in the wrong operating mode Set the heat pump’s heating functions to the correct operating mode.
Thermostats closed on the radiators or underfloor heating Open the thermostats in as many rooms as possible.
Adjust the room temperature in the Setpoint room menu instead of closing the thermostats.
The automation setpoint is too low Increase the comfort setpoint in the Setpoint room menu.
Increase the gradient of the heating curve by changing the values of the Y points in the Heating curve menu.
Set the maximum setpoint for supply water to a sufficiently high value in the Set value output water temp. menu.
The heating circuit’s time programme is on Go to the Time programme heating circuit menu and adjust the time programme.
Air in the heating system Remove the air from the heating system.
Closed valves between the accumulator and the heat supply network Open the valves.
Activated an external contact for decreasing the room temperature Check any external contacts.
High room temperature The setpoints for the heating circuits are too high If the room temperature is only too high during cold weather, decrease the gradient of the heating curve.
If the room temperature is too high during mild weather, decrease the comfort setpoint.
Domestic water is cold The domestic hot water function is not active Set the correct value for the Domestic water operating mode setting.
Domestic hot water consumption too high Wait until the water warms up. When a temporary period of high consumption begins, you may select forced charging of domestic hot water by pressing the domestic hot water button on the user terminal for 3 seconds.
Setpoint too low Go to Domestic water setpoints and increase the setpoint for domestic water.
Supply mixing valve setting too small Open the valve.
Compressor does not start up No need for heat Check the device’s status information in the Info menu.
The minimum compressor stop time is active Wait 20 minutes and check whether the compressor starts up.
The device has a failure Check the reason for the failure in the Info menu and take the necessary measures with the help of the troubleshooting table.